CXVIN Command - Analog Input Calibration

Calibrates voltage readings from the device’s analog inputs (AD).


What is it for?

Use caseDescription
📏 Measurement precisionAdjust readings to actual values
Battery monitoringCalibrate power supply voltage reading
🔧 Factory configurationInitial equipment adjustment
📊 Analog sensorsImprove fuel sensor precision

Description

Allows calibrating the analog-to-digital conversion parameters using the device’s main power supply voltage as reference.

It is essential to verify with a multimeter that the supply voltage is exactly as indicated in the command before executing the calibration.


Commands

Query current factor

QCXVIN

Response

RCXVINaaaa

Calibrate

SCXVINbbbb

Parameters

ParameterDescription
aaaaInternal calibration factor (calibration result)
bbbbApplied voltage in hundredths of volt (e.g.: 2400 = 24.00V)

Calibration Procedure

  1. Power the device with stable voltage (recommended: 24.00 VDC)
  2. Verify with multimeter that the voltage is exact
  3. Send command with the measured value in hundredths

Example

Supply verified at 24.00 VDC:

>SCXVIN2400< >RCXVIN0995<

The value 0995 is the internal adjustment factor calculated for AD readings.